1) Step-up
transformer power – nominal power capacity of Step-Up Transformer (for
reference only).
2) Max U tap of
SU Trans-r – max tap voltage in SU Transformer (for reference only).
3) Nom. U SUT –
nominal input (primary) voltage of SU Transformer (380 V, 480 V, 500 V).
4) Nom. U / F
of power supply – nominal parameters of power supply system (voltage /
frequency).
5) Cable length
/ cross section – nominal parameters of cable line (length / cross section).
6) Max oper. F – max operating
frequency which is used in SUT tap voltage calculation. (It is recommended to run ESP system
exactly at this frequency).
7) Max oper. U – max operating
voltage at Freq. Converter when running at Max oper.
Frequency (it is recommended to use value 320 V for stable operation of ESP
system in case of input voltage drops).
8) Current
limit – actual value of current limit preset in Freq. Controller for the
given motor power capacity.
9) Desired
current lim.: 150% – min recommended current limit in Frequency Converter.
10) Required
tap voltage U in Step-Up Transformer – recommended tap voltage in Step-Up
Transformer which was calculated with all losses in ESP system.
11) Tap voltage
in Step-Up Transformer – selected actual tap voltage in Step-Up Transformer
(it is recommended to choose the tap which is the nearest to recommended).
Use arrows “Up”/”Down” to select window elements.
To change value in window element “list” () hover the cursor
over it and change value with arrows “Left”/”Right” and confirm with Enter.
To change value in window element “parameter” () hover the cursor
over it, start editing with Enter pressing and input new value with figures.
Confirm input with Enter. To leave parameter unchanged press ESC.
Press ESC to return to previous menu.